FSTC of high rise concrete wall

Authors

  • J.L. Feilders Jade Acoustics Inc., 545 North Rivermede Road, Concord, Ont. L4K 4H1, Canada

Keywords:

Acoustic noise, Concrete buildings, Shear walls, Walls (structural partitions), Field sound transmission class, High rise concrete wall

Abstract

Sound transmission loss tests following ASTM E336-84 procedures were carried out in a concrete framed high rise residential buildings. Tests were made on an 8 inch concrete shear wall with laminated drywall each side following initial noise complaints and remedial work. Field test results showed significant differences from FSTC 50 to 56 due to mounting of the drywall.

Additional Files

Published

2001-09-01

How to Cite

1.
Feilders J. FSTC of high rise concrete wall. Canadian Acoustics [Internet]. 2001 Sep. 1 [cited 2024 Sep. 12];29(3):109-. Available from: https://jcaa.caa-aca.ca/index.php/jcaa/article/view/1404