Control of boiler noise in a high rise building

Authors

  • Hugh Williamson Hugh Williamson Associates Inc, 12 Maple Lane, Ottawa, Ont. K1M 1G7, Canada

Keywords:

Boilers, Pipe, Tall buildings, Ventilation exhausts, Boiler noise, Gas pulse fired hot water boilers

Abstract

A case study is presented concerning the control of low frequency noise from gas pulse-fired hot water boilers. Basic acoustic principles of open ended pipes and of expansion chamber mufflers have been used to assist in understanding the nature of the noise problem and devising a solution.

Additional Files

Published

2000-03-01

How to Cite

1.
Williamson H. Control of boiler noise in a high rise building. Canadian Acoustics [Internet]. 2000 Mar. 1 [cited 2024 Nov. 24];28(1):15-9. Available from: https://jcaa.caa-aca.ca/index.php/jcaa/article/view/1260