Case study: The use of 'high-solidity' low noise axial fans to reduce noise from a rooftop air-handling unit

Auteurs-es

  • R.D. Stevens HGC Engineering, 2000 Argentia Road, Plaza 1, Mississauga, Ont. L5N 1P7, Canada

Mots-clés :

Acoustic noise, Acoustic variables measurement, Air conditioning, Fans, Pressure, Speed, Air handling unit, Axial condenser fans, Sound power level

Résumé

A case study was initiated with the aim of controlling the noise from axial (propeller type) condenser fans in an air-handling unit. The unit of concern was a 15 ton heating/cooling unit, with a pair of 30 inches diameter propeller fans used to move outdoor air over the condenser coil. It was found that the newer generation of `high-solidity' low-noise axial fans is an effective means of significantly reducing the noise impact of an existing rooftop air-handling unit.

Fichiers supplémentaires

Publié-e

2001-09-01

Comment citer

1.
Stevens R. Case study: The use of ’high-solidity’ low noise axial fans to reduce noise from a rooftop air-handling unit. Canadian Acoustics [Internet]. 1 sept. 2001 [cité 16 juill. 2026];29(3):82-3. Disponible à: https://jcaa.caa-aca.ca/index.php/jcaa/article/view/1393